序号 | 电压等级 (KV) | 电缆长度 (KM) | 选用装置型号 | 谐振 电压(KV) | 装置额定 电流(A) | 额定输出 容量(KVA) |
1 | 10 | 1 | BCJX-80/40 | 40 | 2 | 80 |
2 | 2 | BCJX-120/20 | 20 | 6 | 120 | |
3 | 3 | BCJX-315/30 | 30 | 10.5 | 315 | |
4 | 4 | BCJX-315/30 | 30 | 10.5 | 315 | |
5 | 5 | BCJX-315/30 | 30 | 10.5 | 315 | |
6 | 35 | 0.5 | BCJX-120/60 | 60 | 2 | 120 |
7 | 1 | *BCJX-315/90 | 90 | 3.5 | 315 | |
BCJX-210/60 | 60 | 3.5 | 210 | |||
8 | 2 | *BCJX-630/90 | 90 | 7 | 630 | |
BCJX-420/60 | 60 | 7 | 420 | |||
9 | 3 | BCJX-600/60 | 60 | 10 | 600 | |
10 | 4 | BCJX-600/60 | 60 | 10 | 600 | |
11 | 5 | BCJX-900/60 | 60 | 15 | 900 | |
12 | 110 | 1 | BCJX-600/120 | 120 | 5 | 660 |
BCJX-660/110 | 110 | 6 | 550 | |||
13 | 2 | BCJX-1320/110 | 110 | 12 | 1320 | |
14 | 3 | BCJX-1980/110 | 110 | 18 | 1980 | |
15 | 4 | BCJX-2640/110 | 110 | 24 | 2640 | |
16 | 5 | BCJX-2640/110 | 110 | 24 | 2640 | |
17 | 220 | 1 | BCJX-2000/200 | 200 | 10 | 2000 |
18 | 2 | BCJX-4000/200 | 200 | 20 | 4000 | |
19 | 3 | BCJX-6000/200 | 200 | 30 | 6000 | |
20 | 4 | BCJX-8000/200 | 200 | 40 | 8000 | |
21 | 5 | BCJX-8000/200 | 200 | 40 | 8000 |
序号 | 电压等级 (KV) | 装置型号 | 额定容量 (KVA) | zui高谐振 电压(KV) | zui大输出 电流(A) | 备注 |
22 | 35 | BCJX-420/120 | 420 | 120 | 3.5 | |
23 | 110 | BCJX-440/220 | 440 | 220 | 2 | |
24 | BCJX-1320/220 | 1320 | 220 | 6 | | |
25 | 220 | BCJX-2000/400 | 2000 | 400 | 5 | |
序号 | 额定电压 (KV) | 机组容量 (MW) | 相电容(uf) | 装置型号 | 额定容量 (KVA) | zui高谐振 电压(KV) | zui大输出 电流(A) |
26 | 6.3~10.5 | 50~100 | 0.15~0.45 | BCJX-40/20 | 40 | 20 | 2 |
27 | 13.8~20 | 125~600 | 0.2 | BCJX-80/40 | 80 | 40 | 2 |
0.4 | BCJX-160/40 | 160 | 40 | 4 | |||
28 | 10~20 | 100~100 | 1.0 | BCJX-600/60 | 600 | 60 | 10 |
2.5 | BCJX-600/60 | 600 | 60 | 25 | |||
注:订货必须提供机组额定容量、额定电压和相电容,以便按fo=50HZ设计配置。 |
型号 | 功率 | 输入电压/电流 | 输出电压/zui大电流(调频调压) |
BCJX-15/0.4 | 15KW | 380V/37. | 0~400V/37. |
BCJX-30/0.4 | 30KW | 380V/7 | 0~400V/7 |
BCJX-75/0.4 | 75KW | 380V/187. | 0~400V/187. |
BCJX-5=100/0.4 | 100KW | 380V/250A | 0~400V/250A |
BCJX-150/0.4 | 150KW | 380V/37 | 0~400V/37 |
型号 | GTK 40/20 | GTK 105/30 | GTK 150/30 | GTK 110/55 | GTK 1650/55 | GTK 330/55 | GTK 500/100 | GTK 1000/100 | |||
额定电压 额定电流 | 20KV/2A | 30KV/3. | 30KV/ | 55KV/2A | 55KV/3A | 55KV/3A | 100KV/ | 100KV/10A | |||
电感量 | 20H | 20H | 20H | 40H | 40H | 40H | 40H | 40H | |||
|
型号 | 容量 | 输入电压 | 输出电压/输出电流(双次级) |
GSB-5/2.2 | 5KVA | 380V | 2×1.1KV/2×2. |
GSB-7.5/2.2 | 7.5KVA | 380V | 2×1.1KV/2×3.7A |
GSB-10/2.2 | 10KVA | 380V | 2×1.1KV/2× |
GSB-10/4 | 10KVA | 380V | 2×2.2KV/2×2. |
GSB-15/4 | 15KVA | 380V | 2×2KV/2×3.7A |
GSB-20/4 | 20KVA | 400V | 2×2KV/2× |
GSB-30/4 | 30KVA | 400V | 2×2KV/2×7. |
GSB-40/4 | 40KVA | 400V | 2×2KV/2×10A |
GSB-60/4 | 60KVA | 400V | 2×2KV/2×1 |
GSB-80/8 | 80KVA | 400V | 2×2KV/2×10A |
GSB-100/8 | 100KVA | 400V | 2×2KV/2×12. |
GSB-120/8 | 120KVA | 400V | 2×2KV/2×1 |
电缆导体截面 积(平方毫米) | 电容量(uf/km) | ||||
YJV、YJLV 6/6KV、6/10KV | YJV、YJLV 8.7/10KV、8.7/15KV | YJV、YJLV 12/20KV | YJV、YJLV 21/35KV | YJV、YJLV 26/35KV | |
1×35 | 0.212 | 0.173 | 0.152 | | |
1×50 | 0.237 | 0.192 | 0.166 | 0.118 | 0.114 |
1×70 | 0.270 | 0.217 | 0.187 | 0.131 | 0.125 |
1×95 | 0.301 | 0.240 | 0.206 | 0.143 | 0.135 |
1×120 | 0.327 | 0.261 | 0.223 | 0.153 | 0.143 |
1×150 | 0.358 | 0.284 | 0.241 | 0.164 | 0.153 |
1×185 | 0.388 | 0.307 | 0.267 | 0.180 | 0.163 |
1×240 | 0.430 | 0.339 | 0.291 | 0.194 | 0.176 |
1×300 | 0.472 | 0.370 | 0.319 | 0.211 | 0.190 |
1×400 | 0.531 | 0.418 | 0.352 | 0.231 | 0.209 |
1×500 | 0.603 | 0.438 | 0.388 | 0.254 | 0.232 |
1×630 | 0.667 | 0.470 | 0.416 | 0.287 | 0.256 |
电缆导体截面 积(平方毫米) | 电容量(uf/km) | ||||
YJV、YJLV 6/6KV、6/10KV | YJV、YJLV 8.7/10KV、8.7/15KV | YJV、YJLV 12/20KV | YJV、YJLV 21/35KV | YJV、YJLV 26/35KV | |
3×35 | 0.212 | 0.173 | 0.152 | | |
3×50 | 0.237 | 0.192 | 0.166 | 0.118 | 0.114 |
31×70 | 0.270 | 0.217 | 0.187 | 0.131 | 0.125 |
3×95 | 0.301 | 0.240 | 0.206 | 0.143 | 0.135 |
3×120 | 0.327 | 0.261 | 0.223 | 0.153 | 0.143 |
3×150 | 0.358 | 0.284 | 0.241 | 0.164 | 0.153 |
3×185 | 0.388 | 0.307 | 0.267 | 0.180 | 0.163 |
3×240 | 0.430 | 0.339 | 0.291 | 0.194 | 0.176 |
3×300 | 0.472 | 0.370 | 0.319 | 0.211 | 0.190 |
3×400 | 0.531 | 0.418 | 0.352 | 0.231 | 0.209 |
3×500 | 0.603 | 0.438 | 0.388 | 0.254 | 0.232 |
3×630 | 0.667 | 0.470 | 0.416 | 0.287 | 0.256 |
电缆导体截面 积(平方毫米) | 电容量(uf/km) | |
YJV、YJLV 64/110KV | YJV、YJLV 128/220KV | |
3×240 | 0.129 | |
3×300 | 0.139 | |
3×400 | 0.156 | 0.118 |
3×500 | 0.169 | 0.124 |
3×630 | 0.188 | 0.138 |
3×800 | 0.214 | 0.155 |
3×1000 | 0.231 | 0.172 |
3×1200 | 0.242 | 0.179 |
3×1400 | 0.259 | 0.190 |
3×1600 | 0.273 | 0.198 |
3×1800 | 0.284 | 0.207 |
3×2000 | 0.296 | 0.215 |
3×2200 | | 0.221 |
3×2500 | | 0.232 |
试品容量(KVA) | 630 | 2000 | 3150 | 6300 | 8000 | 1600 |
类型 | ||||||
高压-底 | 2700 | 4100 | 4600 | 5900 | 7000 | 8200 |
低压-底 | 4200 | 660 | 7900 | 10000 | 11000 | 15300 |
试品容量(KVA) | 50000 | 31500 | 20000 | 10000 | 56000 |
类型 | |||||
高压-中压、低压、地 | 14200 | 11400 | 8700 | 6150 | 4200 |
中压-高压、低压、地 | 24800 | 11800 | 13200 | 9600 | |
低压-高压、中压、地 | 19300 | 19300 | 12000 | 9400 | 6800 |
试 品 型 号 | SEPSL-63000 | SSPSL-120000 | SSPSL-240000 | |
类型 | 高压-中压、低压及地 | 12100 | 13500 | 17050 |
中压-高压、低压及地 | 18500 | 19700 | 23260 | |
低压-高压、中压及地 | 18200 | 23600 | 29940 | |
试 品 型 号 | SFPSL-240000 | SFP-360000 | SFPSZL-120000 | |
类型 | 高压-中压、低压及地 | 32230 | 33910 | 38020 |
中压-高压、低压及地 | | | 23260 | |
低压-高压、中压及地 | 22470 | 23790 | 22160 |
|
部分发电饥的电容值 |
类别 | 型号 | 生产厂家 | 额定容量(MW) | 额定电压(KV) | 相电容(uf) |
汽 轮 发 电 机 | QFS-125-2 | 上海电机厂 | 125 | 13.8 | 0.08~0.12 |
QFSN-200-2 | 哈尔滨电机厂 | 200 | 15.75 | 0.19~0.21 | |
QFQS-200-2 | 东方电机厂 | 200 | 15.75 | 0.1928~0.21 | |
QFQS-200-2 | 北京重型电机厂 | 200 | 15.75 | 0.18~0.19 | |
QFS-300-2 | 上海电机厂 | 300 | 18.0 | 0.16~0.20 | |
QFSN-300-2 | 上海电机厂 | 300 | 18.0 | 0.18~0.20 | |
ATB-2 | 美国GE公司 | 352 | 23.0 | 0.268(设计值) | |
TBB-320-2 | (前苏联) | 320 | 22.0 | 0.31 | |
2-105×234 | 美国西屋公司 | 600 | 20.0 | 0.2(工厂试验值) | |
50WT23E-138 | ABB | 600 | 20.0 | 0.253(设计值) | |
水轮 发电机 | | | 72.5~85 | 10.5 | 0.694 |
| | 300 | 15.75 | 1.7~2.5 | |
| | 400 | 18.0 | 2~2.5 |
电缆额定电压 | 交接试验电压 | 预防性试验电压 | ||
Uo-U | 倍数 | 电压值 | 倍数 | 电压至(KV) |
1.8/3 | 2Uo | 3.6 | 1.6Uo | 3 |
3.6/6 | 2Uo | 7.2 | 1.6Uo | 6 |
6/6 | 2Uo | 12 | 1.6Uo | 10 |
6/10 | 2Uo | 12 | 1.6Uo | 10 |
8.7/10 | 2Uo | 17.4 | 1.6Uo | 14 |
12/20 | 2Uo | 24 | 1.6Uo | 19 |
21/35 | 2Uo | 42 | 1.6Uo | 34 |
26/35 | 2Uo | 52 | 1.6Uo | 42 |
64/110 | 1.7Uo | 109 | 1.36Uo | 87 |
127/220 | 1.4Uo | 178 | 1.15Uo | 146 |
额定电压 KV | zui高工作电压 KV | 线端交流试验电压值KV | 中性点交流试验电压值KV | ||
全部更换绕组 | 部分更换绕 组或交接时 | 全部更换绕组 | 部分更换绕 组或交接时 | ||
<1 | ≤1 | 3 | 2.5 | 3 | 2.5 |
3 | 3.5 | 18 | 15 | 18 | 15 |
6 | 6.9 | 25 | 21 | 25 | 21 |
10 | 11.5 | 35 | 30 | 35 | 30 |
15 | 17.5 | 45 | 38 | 45 | 38 |
20 | 23.0 | 55 | 47 | 55 | 47 |
35 | 40.5 | 85 | 72 | 85 | 72 |
110 | 126.0 | 200 | 170(195) | 95 | 80 |
220 | 252.0 | 360 | 306 | 85 | 72 |
395 | 336 | (200) | (170) | ||
500 | 550.0 | 630 | 536 | 85 | 72 |
680 | 578 | 140 | 120 |
周 期 | 要 求 | ||
低压-底 | (1)全部更换定子绕组并修好后的试验电压如下: | ||
大修前 | 容量 KW | 额定电压UnV | 试验电压V |
小于10000 | 36以上 | 2Un+1000但zui低为1500 | |
10000及以上 | 6000以下 | 2.5U | |
6000~18000 | 2Un+3000 | ||
18000以上 | 按专门协议 | ||
更换绕组后 | (2)交接时按上表的0.8倍执行 (3) 大修前或局部更换定子绕组并修好后试验电压为: | ||
运行20年及以下者 | 1.5Un | ||
运行20年以上与架空线路直接连接者 | 1.5Un | ||
运行20年以上不与架空线路直接连接者 | (1.3~1.5)Un |